Applications & Features
- CDTH series carbon dioxide ( CO2 ) / temperature / humidity transmitters are designed for monitoring & controlling indoor air quality, temperature, and humidity in one unit
- CDTHW is suitable for wall mount and CDTHD is suitable for duct mount
- High-performance NDIR digital sensor and circuit, ensure precise measurement and temperature compensation
- Multiple optional RTD or thermistor sensors, compatible with a variety of control systems
- Stable, reliable, and fast response
- 15 years of CO2 sensor life without maintenance
- All electrical terminals are on the inside bottom, avoid any possible destroy to PCB when wiring(CDTHW)
- Digital technology applied, multiple outputs optional, over voltage and reverse polarity protection, high reliability and anti-interference capability
- Large LCD with the unit indicator( CDTHW ), display carbon dioxide ( CO2 ), temperature and humidity alternatively
Accuracy Table for Temperature/ Humidity
OUTPUTS | T (@10~40°C) | RH (25°C,20~80%RH) |
0~10V DC | <±0.5° | C 3%RH |
4~20mA | <±1.0°C | 5%RH |
RS485/ Modbus | <±0.5°C | 3%RH |
Technical Information
CARBON DIOXIDE (CO2 ) | — |
SENSOR | NDIR sensor, with ABC algorithm* |
SAMPLING METHOD | diffusion |
ACCURACY | (40+3%MV) ppm |
RESPONSE TIME | <10s (30cc/min, low airflow) |
DRIFT | <±10ppm/year |
RANGE | 0~2000ppm (measure range 400~2000ppm) |
OUTPUT | 4~20mA, 0~10V, RS485/Modbus |
TEMPERATURE | — |
T- SENSOR | Digital, RTD or thermistor, see models |
T- RANGE | 0~50°C |
T- ACCURACY | see accuracy table |
T- OUTPUT | 4~20mA, 0~10V, RS485/Modbus or RTD / thermistor |
RELATIVE HUMIDITY | — |
RH - SENSOR | Digital polymer |
RH - RANGE | 0~100%RH |
RH - ACCURACY | see accuracy table |
RH - HYSTERESIS | <±1%RH |
RH - RESPONSE TIME | <10s (25°C, in slow air) |
RH - DRIFT | <±0.5%RH/year |
RH - OUTPUT | 4~20mA, 0~10V, RS485/Modbus |
RH - POWER SUPPLY | 16~28VAC/16-35VDC |
RH - LOAD RESISTANCE | ≤500Ω (Current output),≥2kΩ (Voltage output) |
DISPLAY | — Optional LCD Display (CDTHW) |
D - DISPLAY RESOLUTION | 1ppm, 0.1°C, 0.1%RH |
D - WORKING ENVIRONMENT | 0~50°C, 0~95%RH (Non-cond.) |
D - TEMP. COMPENSATION | 0~50°C |
D - STORAGE TEMPERATURE | -20~60°C |